Search This Blog

Pages

Monday 6 November 2017

SPECIFICATION AND STANDARD FOR STRUCTURAL STEELWORK: GENERAL PART 12 - FIRE PROOFING

1.18         FIRE PROOFING

1.18.1        Scope of Work

Spray-on fireproofing shall be applied to the structural steel members not encased in concrete.

1.18.2       General Requirements

All structural steel members protected by spray-on fireproofing material shall have a minimum of 2 hours fire resistance.

The fireproofing material, its application and finished system shall be to the satisfaction of SCI and in accordance to the current standards set by the local Authorities.

The material shall have the approval of the local Authorities for its use in Singapore. The Contractor shall submit documented evidence of the local Authorities' approval immediately subsequent to award of the Contract.

The thickness of the fireproofing shall be in accordance with the manufacturer's written instructions, satisfying the relevant BS 476 and requirements of the local Authorities.

Spray-on fireproofing shall not erode, delaminate, flake or dust.  The totally exposed members will be subject to the worst weather, heavy rain and strong wind.   The Contractor shall ensure that fireproofing at these areas will not be damaged and its integrity will not be adversely affected under these conditions.
1.18.3       Manufacturer's Literature

The Contractor shall submit the following:

(a) Alternative  equivalent  manufacturer's  trade  name,  if  applicable.  3  samples  of proposed product and 6 copies of applicable technical and installation data. Data submitted shall include chemical and physical descriptions of spray-on fireproofing system, substantiated in writing by an Independent Testing Agency(ITA) and approved by SCI.

(b)    Test data from the approved ITA to verify that the spray-on fireproofing system meets Underwriters' Laboratories Inc (UL) ratings (or other approved fire rating method), performance and contains no asbestos or free crystalline silica, and that after sealer is applied there is no flaking, dusting, delamination or erosion.

1.18.4 Warranty

The Contractor shall submit warranty from the manufacturers of the materials that the spray-on fireproofing will not flake, dust, delaminate or erode.  The Contractor shall also submit warranty of the proposed system by the manufacturers of all other materials used in the system.

1.18.5 Codes and Standards

All spray-on fireproofing shall comply with the applicable requirements of the local Authorities and the requirements of the UL.  In case of any discrepancies, the more stringent requirements shall prevail.

Spray-on  fireproofing  systems  shall  be  tested  in  accordance  with  the  following
Standards:

Fire Tests                   -          ASTM E-1 19, UL 263, or BS 476 : Part 8
Salt Spray Testing     -          ASTM B-1 17
Deflection                   -          ASTM E-759/80
Bond Impact               -          ASTM E-760/80
Cohesion/Adhesion    -          ASTM E-736/80
Compressive Strength-          ASTM E-761/80

1.18.6 Mock-Up and Samples

At least 8 weeks prior to the proposed on-site application of fireproofing, the Contractor shall apply spray-on fireproofing on a mock-up at, a location on site, designated by the S.O..  The mock-up shall be constructed in the same manner and use the same materials as intended for the rest of the works, involving spray-on fireproofing.


The mock-up, if approved, shall form part of the Works and left in an environment similar to that at the actual location.

The Contractor shall submit within 2 weeks after the award of the Contract, samples and manufacturer's technical and installation data to SCI for approval.

Tests on mock-up shall include cohesion/adhesion, thickness, bond impact and other tests as directed by SCI.

Within 7 days of the completion of the tests on the mock-up, the Contractor shall submit a full report on the mock-up for the approval of SCI.  The report shall include but not limited to the following:

(a)       Detail Results of Tests
(b)       Application Procedure

If in the opinion of SCI, the tests on the mock-up fail to comply with the Contract Specification, the Contractor shall submit a new proposal for the testing of additional mock-ups, for the approval of SCI All costs and expenses incurred in the construction and testing of the additional mock-ups shall be borne solely by the Contractor and no extension of time will be granted.


If the tests on the mock-up are accepted by SCI, the Contractor will  be given approval to proceed with the application of spray-on fireproofing to the rest of the work in similar manner to the mock-up and in compliance with the Contract Specification.

1.18.7 Thickness of Fireproofing

The Contractor will provide a thickness schedule for approval, of all the members within 2 weeks after the award of the Contract for approval by SCI.  The proposed thickness shall be supported by approved test reports, which verify that it will provide the specified fire resistance.

1.18.8 Materials

Fireproofing Materials

Monokote MK6 or approved equivalent is to be spray applied to all the structural members not encased in concrete and under internal environment only.  Fendolite or approved equivalent is to be spray applied to all other structural steel members not mentioned in the above paragraph.

Material containing asbestos or mineral wool shall not be permitted.
Spray-on fireproofing shall not erode, delaminate, flake or dust when subjected to an air velocity of at least 5.28 m/s for 24 hours.  Use sealer to prevent erosion, flaking
and dusting.  The Contractor shall submit test data and application procedures of
spray-on fireproofing and sealerSpray-on fireproofing material shall demonstrate that it inhibits corrosion of steel when applied to unpainted steel and tested in accordance with ASTM E-937.

1.18.9 Adhesive

Adhesive, if required by manufacturer, shall consist of a latex-type emulsion which, after setting, is unaffected by moisture or ageing, and shall be furnished by the manufacturer of the spray-on fireproofing system.

1.18.10 Sealer

Sealer, to prevent erosion, flaking or dusting of spray-on fireproofing shall be applied to spray-on  fireproofing  in  accordance  with  the  manufacturers  instructions.    Sealer material shall be as furnished by the manufacturer of the spray-on fireproofing system, and tested as part of the required fire rating assembly.

1.18.11 Storage and Handling

Material shall be delivered in original unopened packages.   Material shall be stored above ground level, under cover and in a dry location, until ready for use.  All bags that have been exposed to water before use or have overrun the expiry dates shall be rejected and removed from the Site.

1.18.12 Workmanship

General

All the work in the section shall be carried out strictly in accordance with the manufacturer's written instructions and the approved Quality Manual.

Detailed Instructions

The Contractor shall obtain from the manufacturer, detailed printed instructions for the proper mixing, application, and/or installation of the manufacturer's products. The Contractor shall furnish a certificate that the materials have been installed in accordance with the manufacturer's printed instructions and field directions.

Refer to Clause 3.5 on "Application" of the Contract Specification hereinafter. Surface Preparation
Bare steel surfaces to receive the spray-on fireproofing, shall be clean and free of dirt, grease, oil, loose plaster, loose rust scale, loose paint, or other conditions, which would prevent good adhesion.

All surfaces to receive spray-on fireproofing, which do not comply with the preceding paragraph, shall be cleaned and all coating or foreign substances, which woulimpair and adversely affect proper adhesion of the spray-on fireproofing system shall be removed.

The Contractor shall not start application until all surfaces and conditions have been examined and prepared by the Contractor and are satisfactory to him to receive the spray-on fireproofing system.

Where the surface is painted for corrosion protection, the Contractor shall ensure that the fireproofing material is compatible with and adhere to the paint coating.  The Contractor shall conduct tests all at his own cost to demonstrate the compatibility and adherence of the fireproofing to the paint work.

1.18.13           Application

The Contractor shall comply with manufacturer's printed instructions for the type of material and condition of substrate in each case and to consult with manufacturer's technical representative at the Site to determine proper procedure for conditions not fully covered by printed instructions.

Type of spray equipment used shall be recommended by the fireproofing manufacturer.

Install thickness markers before spraying.  Extend material full thickness over entire substrate to be covered in a monolithic blanket of uniform texture.

Where required by the manufacturer to meet UL requirements or local Authorities approval, tamp the surface of freshly sprayed fireproofing to provide a medium smooth texture, of the required thickness, minimum fire protection shall be for two (2) hours.

Apply sealer on spray-on surfaces, where specified in the preceding paragraphs, in accordance with manufacturer's directions.

Apply spray-on fireproofing to the thickness necessary to provide fire-resistance rating indicated on the Drawings.

Application of material shall be made as follows:

(a)             Materials that has partially set shall not be used. Do not use caked or lumpy material.  Mix each batch separately.
(b)             Apply spray-on sealer to all fireproofed surfaces.

1.18.14      Fixing of Lath

The Contractor shall submit for approval by the S.O. his method statement for fixing the metal lath to the parent steel surface, where it is required for the application of the spray-on fireproofing.  Any method of fixing that adversely affects the properties and strength of the steel members shall not be approved.

1.18.15     Protection

Prior to start of work, all adjoining finished surfaces shall be covered with a layer of heavy  polyethylene  film,  which  shall  remain  in  place  until  work  of  spray-on fireproofing is completed.

During spraying operations, the Contractor shall provide necessary protection to persons in the vicinity against harm and/or injury and to protect against health hazards from exposure of the spray-on fireproofing.   Spraying operations and protection shall conform to the following and to the current requirements of the local Authorities:-

(a)       Before the start of spraying operations, all floor areas shall be swept broom clean.  Before the application of material, the floor area shall be cleared of all objects, material and equipment other than that employed in the fireproofing works. All objects, materials, etc., shall be covered with plastic or plastic- coated tarpaulin sheets in a manner that precludes the subsequent dispersal of spray-on particles.

(b)       The area of the floor to be fireproofed shall be enclosed with plastic or plastic-coated tarpaulins in a manner, which shall preclude the escape of material from the enclosure.

(c)       Wet material which has fallen to the floor shall be immediately swept up and placed in a container having walls bottom and tight cover strong enough to resist tearing or breaking under normal handling conditions and clearly marked as containing spray-on waste.

(d)       The contents of the aforementioned containers shall not be transferred to another container, but the containers shall be placed directly upon a vehicle for disposal off the Site.

(e)       All floors shall be vacuumed shortly after drying.  The vacuum cleaner shall contain a strong, single-service disposable inner bag of durable material, which shall be removed from the vacuum cleaner and tightly sealed.   The bag shall then be placed in a container of an approved type for removal and disposal.

(f)        The materials used to form the enclosure shall be thoroughly vacuumed upon completion of the application of the fireproofing in the area.  The entire floor area, all ledges and surfaces including tarpaulins upon which waste materials may have fallen, shall then be vacuumed or re-vacuumed before removal of the enclosures.

(g)       Enclosures  shall  not  be  dismantled  until  the  area  has  been  thoroughly vacuumed after completion of spraying and clean-up.

(h)       All areas used for opening bags containing waste material and/or charging of hoppers  shall  be  enclosed  in  such  a manner  that  material  shall  not  be permitted to escape from the immediate area in which such activity takes place. Upon completion of spraying operation, the Contractor shall protect all fireproofing from damage by subsequent building construction operations and effects of weather.  Protection methods shall be as recommended by the manufacturer of the approved spray-on fireproofing system.

1.18.16     Patching and Cleaning

Do all patching, cutting and repairing of damaged or unsatisfactory spray-on fireproofing materials or improper application of spray-on fireproofing as directed by SCI.

Immediately after completion of work in such room or space, clean the adjoining surfaces of  over-spray material and fall-out from the spraying  operation.   Daily sweep working area; place waste materials in suitable containers and remove from the Site.

Upon completion of fireproofing, remove all equipment and clean all deposits from areas, which do not require fire protection Place all waste in suitable containers and remove from Site.

1.18.17     General

The Contractor shall submit for approval by SCI a Quality Manual containing Quality Assurance/Quality Control (QA/QC) programme for the proposed work not more than 2 weeks after the award of the Contract.
The Quality Manual shall include but not limited to the following:- (1)       Organisation Charts and responsibilities
(2)       Inspection procedures and frequencies
(3)       Testing procedures
(4)       Records and documentation of results
(5)       Test equipment

1.18.18     Tests

Unless directed otherwise, the following tests shall be carried out in accordance with the ASTM on the fireproofing applied on the Works to ensure its compliance with the Contract Specification

(1)       Deflection to ASTM E759/80
(2)       Bond Impact to ASTM E760/80
(3)       Cohesion/adhesion to ASTM E736/80 (4)       Density
(5)       Thickness

1.18.19     Frequency of Tests
The frequencies at which testing is to be carried out shall be as follows:- (1)       Deflection as instructed by SCI.
(2)       Bond impact as instructed by SCI.
(3)       Cohesion/adhesion one test location to be selected at a frequency of one per
10-metre length of the structural steel members.
(4)       Density to be at the same frequency as cohesion / adhesion test.
(5)       Tests on the thickness of the fireproofing sprayed on the trusses shall be at a frequency of one per 5 metres length of the structural steel member.  A total of  nine  readings  shall  be  taken  at  two  positions  300mm  apart  and  the average of the eighteen readings shall be determined.

No individual thickness shall be more than 3 mm less than that specified in the design.

The average thickness recorded for each test location shall not be less than that required to achieve the specified fire resistance.




No comments:

Post a Comment